60. Every underground tank installed shall meet one of the following standards:(1) Standards Council of Canada Standard CAN/ULC-S603: Steel Underground Tanks for Flammable and Combustible Liquids;
(2) Standards Council of Canada Standard CAN4/ULC-S615: Reinforced Plastic Underground Tanks for Petroleum Products;
(3) Laboratories of Insurers of Canada ULC/ORD-C58.10: Jacketed Steel Underground Tanks for Flammable and Combustible Liquids.
The tanks that meet the standard referred to in subparagraph 1 and that are equipped with a corrosion protection system referred to in section 61 shall be equipped with accessible testing terminals.